Front Panel Displays Table 23-1
MENU
/DEV
/MAX
DESCRIPTION
INPT
Show input choices
RTD 2.
RTD 3.
RTD.4
INPUT TYPE
2-wire RTD
3-wire RTD

4-wire RTD
DEC.P
Show input choices
FFFF.
FFF.F
DECIMAL POINT
RD.CF
R.1
F
C
READING CONFIGURATION
Display in░F
Display in ░C
S1.CF
S.1=


S.2=
A
B

U
L
SETPOINT 1 CONFIGURATION:
A: Active above
B: Active below

U: Unlatched
L: Latched
S2.CF
S.1=


S.2=
A
B

U
L
SETPOINT 2 CONFIGURATION:
A: Active above
B: Active below

U: Unlatched
L: Latched
S1.DB
Scroll right one digit Change the flashing digit's value SETPOINT 1 DEADBAND
Select from 0000 through 9999
(Factory preset: 0003).
S2.DB
Scroll right one digit Change the flashing digit's value SETPOINT 2 DEADBAND
Select from 0000 through 9999
(Factory preset: 0003).
OT.CF
0.1



0.2



0.3


0.4


0.5
D

E


V
C

O
P

D
R

F
H
OUTPUT CONFIGURATION
Analog Output:
D: Disabled
E: Enabled

V: Voltage analog out
C: Current analog out

O: Proportional to reading
P: Proportional to Setpoint 1

D: Direct reading
R: Reverse acting

F: 0-10 V proportional
H: 0-5 V proportional
Note: If you select 0.2 = V, you may select your analog output to be 0-10 V or 0-5 V by accessing submenu 0.5. If you select 0.3=P, you may select your proportional output analog to be direct or reverse acting (4-20 or 20-4).
OT.S.O
Enter new value and show:
OUT1.

Enter new value and show:
RD 2.

Enter new value and show
OUT2.
Show RD 1 and prior value entered.

Scroll right one digit


Prior value entered.


Scroll right one digit


Prior value entered.

Scroll right one digit

Change the flashing digit's value





Change the flashing digit's value



Change the flashing digit's value
OUTPUT SCALE AND OFFSET
P.BND
Scroll right one digit Change the flashing digit's value PROPORTIONAL BAND
Select from 0000 through 9999
M.RST
Scroll right one digit Change the flashing digit's value MANUAL RESET
Select from -1999 through 9999
MENU
/DEV
/MAX
RESET
DESCRIPTION
PEAK
Shows the peak reading and must be pressed again to return to the normal operating mode without resetting. Reset the peak reading when in this mode. Peak Reading
Shows the highest reading since last reset.
SP.RS
LATCHED RESET
Pressing the RESET button will reset your setpoints.
DEV
Shows the difference between the display reading and the setpoint 1 value.
Tunes the propor-tional control if 0.3=P. Goes back to "run" mode if 0.3=A

Setpoint Configuration Displays Table 24-1
MENU
/DEV
/MAX
DESCRIPTION
SP1
Scroll right one digit
Change the flashing digitÆs value
SETPOINT 1
Select from -1999 through 9999
SP2
Scroll right one digit
Change the flashing digitÆs value
SETPOINT 2
Select from -1999 through 9999